Equipment designed and manufactured according to national and international standards and specifications, for outdoor substations and voltage decrease or increase applications, as well as to supply three-phase industrial loads.
Applications:
§ Generator type transformer
§ Substation type transformer
§ Regulator type transformer
§ Rectifier type transformer
§ Mobile substations
General Specifications
Rating:
Single-phase: 5 to 20 MVA
Three-phase: 5 to 60 MVA
Cooling type:
OA, OA/FA, OA/FA/FA, OA/FA/FOA, FOA
Operating frequency:
60 Hz
Primary voltage:
13.8 to 161 kV
Secondary voltage:
2.4 to 34.5 kV
Temperature increase:
131, 149 or 131/149 Fahrenheit in an environment of 104 maximum and 86 Fahrenheit on average in a 24-hour period.
Insulating liquid:
Mineral oil
Back to Transformers